{"borough":"Hounslow","application_type":"All Other","decision":"Approved","decision_conditions":["Condition : 1 - The development hereby permitted shall be carried out in accordance with the following approved plans and specifications: [insert plan numbers/documents].\r\nReason: In order to ensure the development is carried out in accordance with the planning permission.","Condition : 2 - a) The cumulative measured or calculated rating level of noise emitted from the mechanical services plant including heating, ventilation and air conditioning (HVAC) to which this permission refers, shall be 5dB(A) below the existing background noise level, at all times that the plant operate. The measured or calculated noise levels shall be determined at the boundary of the nearest ground floor noise sensitive premises or one metre from the facade of the nearest first floor (or higher) noise sensitive premises, and in accordance to the latest British Standard 4142. An alternative position for assessment/measurement may be used to allow ease of access, this must be shown on a map and noise propagation calculations detailed to show how the design criteria are achieved. \r\n\r\nb) The plant shall be isolated on adequate proprietary anti-vibration mounts to prevent the structural transmission of vibration and regenerated noise within adjacent or adjoining premises, and these shall be so maintained thereafter.   \r\n\r\nc) Following installation of any mechanical services plant including heating, ventilation and air conditioning (HVAC) to which the application refers, a post completion noise assessment shall be submitted for approval to the local planning authority which demonstrates the actual measured rating level of plant operating under normal conditions. All measurements shall be made in accordance with the methodology of BS4142: 2014 (Methods for rating and assessing industrial and commercial sound) and/or its subsequent amendments. The post completion report shall be both completed and submitted to the local authority within 28 days of completion of the installation for review. If the plant fails to meet the specified standard, remedial measures shall be put in place immediately and the noise assessment shall be carried out again.  This shall be repeated until the assessment has reached the required standard.  Once achieved, the plant shall be maintained permanently there"],"last_synced":"2026-06-28T02:30:03.362Z","centroid_northing":177650,"url_planning_app":"https://planningandbuilding.hounslow.gov.uk/NECSWS/ES/Presentation/Planning/OnlinePlanning/OnlinePlanningOverview?applicationNumber=P/2025/2622","lpa_app_no":"P/2025/2622","site_number":1,"ward":"Osterley & Spring Grove","locality":"Brentford","last_date_consultation_comments":"24/09/2025","date_building_work_started_under_previous_permission":null,"description":"Installation of new plant on the southern elevation of the existing building.","parking_details":null,"postcode":"TW8 9ZB","appeal_status":null,"cil_liability":false,"date_building_work_completed_under_previous_permission":null,"pp_id":"14156131","status":"Approved","last_updated_by":"Planning Portal ingest","polygon":{"geometries":[{"coordinates":[[[516405.92203867104,177663.71314526914],[516410.6260823628,177656.16902318154],[516408.21936233365,177654.52899664035],[516416.09590060764,177642.9394757481],[516423.7536461515,177647.6408851677],[516415.87710787763,177659.99575177438],[516414.2361624036,177658.57439544002],[516409.5321187126,177666.22785263357],[516405.92203867104,177663.71314526914]]],"type":"Polygon"}],"type":"geometrycollection"},"wgs84_polygon":{"coordinates":[[[-0.324744,51.485842],[-0.324745,51.485815],[-0.324788,51.485816],[-0.324787,51.485843],[-0.324744,51.485842]]],"type":"Polygon"},"appeal_decision_date":null,"secondary_street_name":null,"lapsed_date":"13/11/2028","bo_system":"Northgate M3","decision_date":"14/11/2025","centroid_easting":516415,"actual_commencement_date":null,"id":"Hounslow-P_2025_2622","lpa_name":"Hounslow","decision_target_date":"23/12/2025","valid_date":"28/10/2025","development_type":"Minor all other minor developments","last_updated":"2026-06-27T13:08:24.025Z","subdivision_of_building":"southern elevation of the existing building","reference_no_of_permission_being_relied_on":null,"centroid":{"lat":51.485829,"lon":-0.324766},"decision_process":null,"application_type_full":"Full planning permission","decision_agency":"Borough","street_name":"Ryan Drive","appeal_decision":null,"title_number":null,"site_name":"Unit","appeal_start_date":null,"application_details":{"affordable_housing_fast_track":false,"phasing_details":[{"phase_detail":"Entire development","intended_completion_date":"11/2025","intended_commencement_date":"09/2025"}],"total_gia_gained":0,"site_area":0.019,"total_gia_lost":0,"total_gia_existing":0,"projected_cost_of_works":"Up to £2m","occupation_status":"Occupied","scheme_phasing":true,"rain_water_harvesting":false,"grey_water_reuse":false,"green_suds":false,"surface_water_discharge_percentage_reduction":0,"non_residential_details":{"total_non_resi_gross_internal_floor_area_to_be_gained":0,"total_non_resi_gross_internal_floor_area_to_be_lost":0,"total_gia_gained":0,"total_gia_lost":0,"total_gia_existing":0},"garden_land_lost":false,"infrastructure_details":{"total_annual_pm_emissions":0,"no_resi_units_to_have_full_fibre":0,"green_roof_area":0,"urban_greening_factor_score":0,"no_homes_passive_cooling":0,"no_new_water_connections_required":0,"no_non_resi_units_to_have_full_fibre":0,"total_annual_nox_emissions":0,"waste_provision":false,"percentage_demolition_construction_material_recycling":0,"no_homes_to_have_electrical_heating":0,"mobile_network_operators_consultation":false,"fire_suppression_system_proposed":false,"no_new_gas_connections_required":0,"ghg_reduction_over_building_regulations":false},"internal_resi_water_usage":0,"ownership_status":"Private"},"epc_number":null,"uprn":10093768880,"actual_completion_date":null}